As a guest user you are not logged in or recognized by your IP address. You have
access to the Front Matter, Abstracts, Author Index, Subject Index and the full
text of Open Access publications.
To address the problem that indirect evaporative cooling technology is limited in high humidity areas, this paper establishes an evaporative cooling system with dehumidification system, which uses the waste heat of data center and solar energy as the regenerative heat source of dehumidification bed, and introduces the selection method of the main equipment of this system; the performance of data center using this system in Guangzhou is analyzed and compared with the conventional mechanical refrigeration system. The results show that the PUE of the conventional mechanical cooling system is 1.4, and the PUE of the combined heat source system is 1.21, which is better than that of the conventional mechanical cooling system; the power consumption and carbon emission of the combined heat source system are much lower than that of the conventional cooling system, which shows a superior energy saving level.
This website uses cookies
We use cookies to provide you with the best possible experience. They also allow us to analyze user behavior in order to constantly improve the website for you. Info about the privacy policy of IOS Press.
This website uses cookies
We use cookies to provide you with the best possible experience. They also allow us to analyze user behavior in order to constantly improve the website for you. Info about the privacy policy of IOS Press.