On account of Main transformer CT (current transformer)’s wrong connection leading to additional circuit, differential loop’s circuit is calculated according to transformer’s load status. Detail analysis is made. In conclusion, potential fault trip exists in RCS-978E stable ratio differential protection. Measures are brought forward to avoid fault trip, so that reliability of transformer protection is improved.